rp54xx Servers may be installed into
E-Series and approved Non- E-Series cabinets using stationary L-bracket
rail assembly kits listed below. | Cabinet Type | Rail Kit Product Number |
|---|
| E-Series HP Cabinet | A5575A | | Other Approved HP Cabinet | A5562A |
Identifying
Approved Non-E-Series HP Cabinets |  |
Approved Non- E-Series cabinets
have black frames, one piece outside sheet metal skins, a partial
return flange, and requires the
installation of the aluminum spacer blocks, supplied with the rail
kits. Approved Non- E-Series cabinets include the following product
numbers: A1883A, A1884A, A1896A, A1897A, C1897A, C2785A, C2786A,
and C2787A. Identifying
E-Series HP Cabinets |  |
E-Series cabinets have light gray
frames, sectioned, plastic outside “skins”, a
full return flange, and does not require
the installation of the aluminum spacer block supplied, with the
rail kits. E-Series cabinets include the following product numbers: A5134A,
A5136A, A5136A, A4900A, A4901A, A4902A, J1500A, J1502A, and J1502A. Identifying
Static Rail Kit |  |
Hewlett-Packard has currently approved
two static rail kits for use in cabinet mounting the rp54xx Server. They
are illustrated below. Installing
Stationary Rails |  |
The
installation of stationary rails is similar for most cabinet and
rail combinations. The key considerations are: Ensure that all safety precautions
are read, understood, and observed Follow all installation instructions provided with
the cabinet and rail kits, and Ensure that the rails extend out from the cabinet
posts sufficiently to properly and safely support the equipment
being installed.
To install an rp54xx Server on stationary rails in an approved
cabinet proceed as follows: Locate the rail mounting height in the cabinet.
Allow for the following space requirements: For each rp54xx Server, allow 31.8cm
(12.5 inches) vertically (7 EIAs or Rack Units (RUs). If installing the A5575A rail kit, allow an additional vertical 4.45cm (1.75
inches (1 EIA) each set of rails.
Install sheet metal nut(s) in the vertical cabinet posts
at the required height for the kit being installed: Install the first nut either: 4.45 cm (1.75 Inches) above the top,
or 31.8 cm (12.5 inches) below the bottom of the last
server.
If installing a A5562A rail kit, install the second
nut in the next frame hole below the first.
Hold the rail in place and insert and tighten the screws.
For installation of other qualified cabinet and rail combinations
refer to the safety precautions and instructions accompanying them.
|