Jump to content United States-English
HP.com Home Products and Services Support and Drivers Solutions How to Buy
» Contact HP
More options
HP.com home
Superdome Site Preparation Guide: HP 9000 Systems > Chapter 1 System Specifications

Electrical Specifications

» 

Technical documentation

Complete book in PDF
» Feedback
Content starts here

 » Table of Contents

 » Index

This section provides electrical specifications for Superdomes.

Grounding

The site building shall provide a safety ground/protective earth for each AC service entrance to all Superdome cabinets.

This equipment is CLASS 1 and requires full implementation of the grounding scheme to all equipment connections. Failure to attach Protective Earth results in loss of regulatory compliance and creates a possible safety hazard.

Circuit Breaker

Each Superdome cabinet using a 3-phase, 4-wire input requires dedicated circuit breaker to support the Marked Electrical current of 44A per phase. The facility electrician and local service codes will determine proper circuit breaker selection.

Each Superdome cabinet using a 3-phase 5-wire input requires a dedicated circuit breaker to support the Marked Electrical current of 24A per phase. The facility electrician and local service codes will determine proper circuit breaker selection.

NOTE: See Table E-1 “Typical Superdome Configurations” for systems that are configured with less than a full compliment of cell boards, memory, and I/O modules.When using the minimum sized breaker, always choose circuit breakers with the maximum allowed trip delay to avoid nuisance tripping.As of March, 2002, PDCA Options 4 and 5 are obsolete.

Detailed site power information is required to configure the system correctly and prevent delays in system installation. Collect the following information from the customer site electrician before selecting the appropriate PDCA.

  • Type of source available 4-wire_____ 5-wire_____

  • Source voltage phase-to-phase _____ Vac

  • Source voltage phase-to-neutral _____Vac

Using the above information, determine the appropriate power option from Table 1-6 “Available Power Options”.

  1. Select the source type that matches the customer source.

  2. Within the matching Source Type selection, select the matching voltage range to the customer's source voltage.

  3. Select the appropriate PDCA.

  4. The customer must either provide the correct mating in-line connector or order one from HP. See Table 1-8 “Options 006 and 007 Specifics” for details.

Example 1-1 The customer has a 3-phase source with a Source Voltage of 208 VAC measured phase-to-phase indicating that a 4-wire PDCA is required.

Example 1-2 The customer has a 3-phase source with a Source Voltage of 220 VAC measured phase-to-neutral indicating that a 5-wire PDCA is required.

Example 1-3 The customer has a 3-phase source with a Source Voltage of 230 VAC measured phase-to-phase indicating that a 4-wire PDCA is required.

Example 1-4 The customer has a 3-phase source with a source voltage of 415 VAC measure phase-to-phase and a measured phase-to-neutral source voltage of 240 VAC, indicating a 5-wire PDCA is required.

Input Power Options

Table 1-6 “Available Power Options” describes the available power options:

Table 1-6 Available Power Options

PDCA Product Number

Source Type

Source Voltage (nominal)PDCA
Required
Input Current Per Phase 200-240 VAC In-line Connector Required

A5800A
Option 001[1]

3-phase

Voltage range 200-240 VAC, phase-to-neutral, 50/60 Hz
(EUR typical)[2]
5-wire24A Maximum per phase

None required. Electrician must hard wire power to the PDCA[3]

A5800A
Option 002a
3-phase Voltage range 200-240 VAC, phase-to-phase, 50/60 Hz
(US typical)
4-wire44A Maximum per phaseNone required. Electrician must hard-wire power to the PDCAc
A5800A
Option 004[4]
3-phase Voltage range 200-240 VAC, phase-to-phase, 50/60 Hz
(US typical)
4-wire44A Maximum per phaseIn-line connector and plug provided with a 2.5-meter power cable. Electrician must hard-wire in-line connector to 100A site power.c,[5]

A5800A
Option 005d

3-phase

Voltage range 200-240 VAC, phase-to-neutral, 50/60 Hz
(EUR typical)
5-wire24A Maximum per phase

In-line connector and plug provided with a 2.5-meter power cable. Electrician must hard-wire in-line connector to 60/63A site power.c,e,[6]

A5800A
Option 006[7]

3-phase

Voltage range 200-240 VAC, phase-to-phase, 50/60 Hz4-wire44A Maximum per phase

2.5meter UL power cord and UL approved plug provided. The customer must provide the mating in-line connector or purchase quantity one A6440A opt 401 to receive a mating inline connector. An electrician must hard wire the in-line connector to 60A/63A site power.c,f,[8]

A5800A
Option 007[9]

3-phase

Voltage range 200-240 VAC, phase-to-neutral, 50/60 Hz5-wire24A Maximum per phase

2.5meter <HAR> power cord and VDE approved plug provided. The customer must provide the mating in-line connector or purchase Quantity 1 A6440A opt 501 to receive a mating in line connector. An electrician must hard wire the in-line connector to 30A/32A site power.c,h,[10]

[1] Options 1 and 2 have been deleted.

[2] 415 VAC phase-to-phase is possible.

[3] A dedicated branch is required for each PDCA installed.

[4] Options 4 and 5 have been deleted.

[5] Refer to Table 1-7 “Option 004 and 005 Specifics” for detailed specifics related to this option.

[6] In the U.S.A., site power is 60 Amps; In Europe site power is 63 Amps.

[7] Customer must provide in-line connector or purchase A6440A option 401.

[8] Refer to Table 1-8 “Options 006 and 007 Specifics” for detailed specifics related to this option.

[9] Customer must provide in-line connector or purchase A6440A option 501.

[10] In the U.S.A., site power is 30 Amps; In Europe site power is 32 Amps.

 

Table 1-7 Option 004 and 005 Specifics[1]

PDCA Product Number

Attached Power Cord

Attached Plug

Connector Provided

A5800A Option 004

OLFLEX 190 (PN 600404) is a 2.5 meter multi conductor, 600 volt, 90 degree C, UL and CSA approved, oil resistant flexible cable. (100 A capacity)

Mennekes
ME 4100P9
(100 A capacity)

Mennekes
ME 4100C9
(100 A capacity)

A5800A Option 005

H07RN-F (OLFLEX PN 1600111) is a 2.5 meter heavy duty neoprene jacketed harmonized European flexible cable. (63 A capacity)

Mennekes
ME 563P6-1235
(63 A capacity)

Mennekes
ME 563C6-1245
(63 A capacity)

 

Table 1-8 Options 006 and 007 Specifics

Customer-Provided Part

PDCA
Product Number

Attached Power Cord

Attached Plug

In-Line ConnectorPanel-Mount Receptacle

A5800A
Option 006

OLFLEX 190 (PN 600804), four-conductor, 6-AWG (16-mm2), 600-Volt, 60-Amp, 90-degree C, UL, and CSA approved, conforms to CE directives GN/YW ground wire.

Mennekes
ME 460P9 3-phase, 4-wire, 60-amp, 250-volt, UL approved. color blue, IEC 309-1, IEC 309-1, grounded at 3:00 o'clock.

Mennekes
ME 460C9 3-phase, 4-wire, 60-amp, 250-volt, UL approved. color blue, IEC 309-1, IEC 309-1, grounded at 9:00 o'clock.[1]

Mennekes
ME 460R9 3-phase, 4-wire, 60-amp, 250-volt, UL approved. color blue, IEC 309-1, IEC 309-1, grounded at 9:00 o'clock.[2]

A5800A
Option 007
Five conductors, 10-AWG (6-mm2), 450/475-volt, 32-amp, <HAR> European wire cordage, GN/YW ground wire.

Mennekes
ME 532P6-14 3-phase, 5-wire, 32-amp, 450/475-volt, VDE certified, color red,
IEC 309-1,
IEC 309-2, ground at 6:00 o'clock.

Mennekes
ME 532C6-16
3-phase, 5-wire, 32-amp, 450/475-volt, VDE certified, color red,
IEC 309-1,
IEC 309-2, ground at 6:00 o'clock.[3]

Mennekes ME532R6-1276
3-phase, 5-wire, 32-amp, 450/475-volt, VDE certified, color red,
IEC 309-1,
IEC 309-2, ground at 6:00 o'clock.b

[1] In-line connector is available from HP by purchasing A6440A, Option 401.

[2] Panel-mount receptacles must be purchased by the customer from a local Mennekes supplier.

[3] In-line connector is available from HP by purchasing A6440A, Option 501.

 

NOTE: A qualified electrician must wire the PDCA in-line connector to site power using copper wire and in compliance with all local codes.


Each branch circuit used within a Superdome Complex must be connected together to form a common ground.

When only one PDCA is to be installed in a Superdome, it must be installed as PDCA 0. Refer to Figure 1-5 “PDCA Locations” for PDCA 0 location.

WARNING! Do not install a PDCA that does not have one of the following set of labels attached.

Figure 1-5 PDCA Locations

PDCA Locations

Power Cords

This section discusses the different possibilities for Superdome PDCA power cords.

Pre-wired PDCAs Options 6 and 7

All Superdomes are delivered with the appropriate cable and plug. The mating in-line connector is not provided.

IMPORTANT: Verify that the source power is correct for the appropriate PDCA wiring.
NOTE: When installing the power connector, allow enough room for mating the connector with the plug.

Check the voltages at the connector prior to connecting the newly installed connector to the PDCA plug. Refer to Figure 1-7 “Four-Wire In-Line Connector (A4660A Opt 401)” and Figure 1-8 “Five-Wire In-Line Connector (A4660A Opt 501)” for pin locations.

  • To verify the proper wiring for a 4-wire PDCA, use a DVM to measure the voltage at the in-line connector. Voltage should read 200 - 240 Vac phase-to-phase as measured between the connector pins as follows: L1 to L2, L2 to L3, L1 to L3.

  • To verify the proper wiring for a 5-wire PDCA, use a DVM to measure the voltage at the connector. Voltage should read 200 - 240 Vac phase-to-neutral as measured between the connector pins as follows: L1 to N, L2 to N, L3 to N.

Figure 1-6 PDCA Assembly for Options 6 and 7 (4-Wire Unit Shown)

PDCA Assembly for Options 6 and 7 (4-Wire Unit Shown)
IMPORTANT: Ensure that your DVM is capable of measuring AC voltages of at least 500VAC. A number of 5-wire power distribution systems may have phase-to-phase voltages in excess of 400VAC. Many hand-held volt meters are limited to 300VAC.

Figure 1-7 Four-Wire In-Line Connector (A4660A Opt 401)

Four-Wire In-Line Connector (A4660A Opt 401)

Figure 1-8 Five-Wire In-Line Connector (A4660A Opt 501)

Five-Wire In-Line Connector (A4660A Opt 501)

Cable Removal

Some installations may either require or desire that the Superdome(s) be hardwired in lieu of using the standard plugs and connectors provided. In these cases, it is necessary to remove the installed power cable from the PDCA. The following procedures are used to remove and replace the existing power cable.

To remove the existing cable from the PDCA, begin be removing the five T-10 Torx screws detailed in Figure 1-9 “PDCA Cable Access (5-Wire Unit Shown)”. Then remove the bottom panel of the PDCA. Retain the panel and screws for future use.

NOTE: The cable removal and installation requires only the bottom panel to be removed. For image clarity, Figure 1-9 “PDCA Cable Access (5-Wire Unit Shown)” does not show cable or cable strain relief.
  1. Locate and remove the PDCAs.

  2. Remove the five screws securing the bottom of the PDCA. Retain the screws. Refer to Figure 1-9 “PDCA Cable Access (5-Wire Unit Shown)” for details.

  3. Disconnect the existing wires from the PDCA terminal lugs. Refer to Figure 1-9 “PDCA Cable Access (5-Wire Unit Shown)” for details.

    NOTE: Loosen the cable side terminal lugs only. Do not loosen the PDCA side terminal lugs.For 5-wire cables, loosen four lugs. For 4-wire cables, loosen three lugs.
  4. Using an 11-mm socket, remove the safety ground cable (green and yellow cable). Retain the attaching hardware.

  5. Remove the cable from the PDCA. Keep all retaining hardware for use during installation of the new cable.

Figure 1-9 PDCA Cable Access (5-Wire Unit Shown)

PDCA Cable Access (5-Wire Unit Shown)

Figure 1-10 PDCA Input Wiring Connections (5-Wire Unit Shown)

PDCA Input Wiring Connections (5-Wire Unit Shown)

Cable Installation

NOTE: These procedures may be used for early deliveries consisting of either option 1 or option 2 as well as those later systems delivered with PDCA cables attached.

Select the proper cable using the following criteria.

  • Each Superdome cabinet using a 3-phase, 4-wire input is required to have a four-conductor cable. The four-conductor cable selected by the facility electrician shall be in accordance with local electrical codes to support the selected circuit breaker for the maximum Product Label current of 44A per phase. The facility electrician and local electrical codes will determine proper power cord selection dependent upon desired application such as rigid conduit, flexible conduit, or cable bundle. Observe derating factors for multiple wires per cable.

  • Each Superdome cabinet using a 3-phase 5-wire input is required to have a five-conductor cable. The five-conductor cable selected by the facility electrician shall be in accordance with local electrical codes to support the selected circuit breaker for the maximum Product Label current of 24A per phase. The facility electrician and local electrical codes will determine proper power cord selection dependent upon desired application such as rigid conduit, flexible conduit, or cable bundle. Observe derating factors for multiple wires per cable.

  1. Prepare the new cable as shown in Figure 1-11 “Cable Preparation Detail”.

  2. Using the cable retaining hardware saved from the cable removal, route the new cable into the PDCA.

  3. Route the cable into the PDCA terminal lugs and secure in position by tightening the lugs.

  4. Using the hardware that was retained during the cable removal, attach the green and yellow ground cable.

  5. Using the five screws retained from the removal procedure, replace the bottom panel on the PDCA. Refer to Figure 1-9 “PDCA Cable Access (5-Wire Unit Shown)” for panel installation details.

  6. To verify the proper wiring to a 4-wire PDCA, use a DVM to measure the voltage at the test points. Voltage should read 200 - 240 Vac phase-to-phase as measured between the test points as follows: L1 to L2, L2 to L3, L1 to L3.

    IMPORTANT: In some electrical distributions around the world, it is possible to measure 415 VAC phase-to-phase. Ensure that your DVM is capable of measuring AC voltages of at least 500VAC. A number of 5-wire power distribution systems may have phase-to-phase voltages in excess of 400VAC. Many hand-held volt meters are limited to 300VAC.

    To verify the proper wiring to a 5-wire PDCA, use a DVM to measure the voltage at the test points. Voltage should read 200-240VAC phase-to-neutral, as measured between the test points as follows: L1 to N, L2 to N, L3 to N.

Figure 1-11 Cable Preparation Detail

Cable Preparation Detail
NOTE: Dimensions shown are for a cable strain relief without an extension nipple. If an extension nipple is used, then the cable jacket must removed accordingly. Figure 1-11 “Cable Preparation Detail” shows a 4-wire cable for illustrative purposes only. 5-wire cable is dimensionally identical regarding insulation and jacket removal. The only exception is the number of conductors.

Figure 1-12 PDCA (Five Wire) Input Wiring Connections

PDCA (Five Wire) Input Wiring Connections

Figure 1-13 PDCA (Four Wire) Input Wiring Connections

PDCA (Four Wire) Input Wiring Connections

Customer Installation Options

Figure 1-14 “PDCA Conduit Connection” and Figure 1-15 “Conduit Required for PDCA Connection” detail a suggested configuration for connecting the PDCA when the use of rigid conduit is required or desired. Using a 2- to 4-inch nipple and a 90o elbow allows the conduit to pass through the raised floor at a point immediately past the cabinet. This prevents the conduit from extending beyond the cabinet.

Figure 1-14 PDCA Conduit Connection

PDCA Conduit Connection

Figure 1-15 Conduit Required for PDCA Connection

Conduit Required for PDCA Connection

System Power Requirements

Table 1-9 “Power Requirements (without Support Management Station)” and Table 1-10 “Component Power Requirements (without Support Management Station)” list the AC power requirements for a Superdome. These tables provide information to help determine the amount of AC power needed for your computer room.

Table 1-9 Power Requirements (without Support Management Station)

RequirementsValueComments
Nominal input voltage 200/208/220/230/240 VAC 
Input voltage range (minimum - maximum)200 - 240 VACAutoselecting (measured at input terminals)
Frequency50/60 Hz 
Number of phases3 
Maximum inrush current 90 A peak 
Product Label maximum current, 3-phase, 4-wire

44 A max

Per phase at 200-240VAC

Product Label maximum current, 3-phase, 5-wire

24 A max

Per phase at 200-240VAC

Power factor correction0.95 minimum 
Ground leakage current (mA)> 3.5 maSee WARNING below.

 

WARNING! Beware of shock hazard. When connecting or removing input power wiring, always connect the ground wire first and disconnect the ground wire last.

Component Power Requirements

Table 1-9 “Power Requirements (without Support Management Station)” and Table 1-10 “Component Power Requirements (without Support Management Station)” list the AC power requirements for a Superdome. These tables provide information to help determine the amount of AC power needed for your computer room.

Table 1-10 Component Power Requirements (without Support Management Station)

Power Required (50/ 60 Hz)VA
Maximum configuration Superdome (32-Way)12,196[1],[2]
Cell Board900
I/O Cardcage500

[1] A number that should be used for planning to allow for enough power to upgrade through the life of the system.

[2] Use Appendix A to determine the actual values required for your system.

 

I/O Expansion Cabinet Power Requirements

The I/O expansion cabinet requires a single phase 200-240VAC input. Table 1-11 “I/O Expansion Cabinet Power Requirements (without Support Management Station)” lists the AC power requirements for the I/O expansion cabinet.

NOTE: The IOX accommodates two AC inputs for redundancy

Table 1-11 I/O Expansion Cabinet Power Requirements (without Support Management Station)

RequirementsValue
Nominal input voltage 200-240 VAC
Input voltage range (minimum-maximum)200-240 VAC
Frequency range (minimum-maximum)50/60 Hz
Number of phases1
Marked Electrical input current16A max
Maximum inrush current 60 A peak
Power factor correction0.95 minimum

 

Table 1-12 I/O Expansion Cabinet Component Power Requirements

Power Required (50 - 60 Hz)

VA

Fully configured cabinet

3200

I/O cardcage

500

ICE

600

 

I/O Expansion Cabinet Power Cords

Table 1-13 “I/O Expansion Cabinet AC Power Cords” lists the power cords for the I/O expansion cabinet.

Table 1-13 I/O Expansion Cabinet AC Power Cords

Part Number A5499AZWhere UsedConnector Type
-001North AmericaL6-20
-002InternationalIEC 309

 

Peripheral Cabinet Power Requirements

There is a high probability that an existing peripheral cabinet may be incorporated into this system. Ensure that adequate power is available for this cabinet and the associated peripherals.

Support Management Station Power Requirements

Refer to the applicable documentation for the SMS power requirements.

Printable version
Privacy statement Using this site means you accept its terms Feedback to webmaster
© 2002 Hewlett-Packard Development Company, L.P.