| United States-English |
|
|
|
![]() |
Site Preparation Guidehp Integrity Superdome andhp 9000 Superdome > Chapter 5 Facility GuidelinesElectrical and Environmental Guidelines |
|
Proper design and installation of a power distribution system for a server requires specialized skills. Those responsible for this task must have a thorough knowledge and understanding of appropriate electrical codes and the limitations of the power systems for computer and data processing equipment. In general, a well-designed power distribution system exceeds the requirements of most electrical codes. A good design, when coupled with proper installation practices, produces the most trouble-free operation. A detailed discussion of power distribution system design and installation is beyond the scope of this document. However, electrical factors relating to power distribution system design and installation must be considered during the site preparation process. The electrical factors discussed in this section are:
Inside the computer room, fire protection and adequate lighting (for equipment servicing) are important safety considerations. Federal and local safety codes govern computer installations. The National Fire Protection Association’s Standard for the Protection of Electronic Computer Data Processing Equipment, NFPA 75, contains information on safety monitoring equipment for computer rooms. Most computer room installations are equipped with the following fire protection devices:
Additional safety devices are:
Adequate lighting and utility outlets in a computer room reduce the possibility of accidents during equipment servicing. Safer servicing is also more efficient and, therefore, less costly. For example, it is difficult to see cable connection points on the hardware if there is not enough light. Adequate lighting reduces the chances of connector damage when cables are installed or removed. The minimum recommended illumination level is 70 foot-candles (756 lumens per square meter) when the light level is measured at 30 inches (76.2 cm) above the floor. This equipment is designed to operate over a wide range of voltages and frequencies. It has been tested and shown to comply with EMC Specification EN50082. However, damage can occur if these ranges are exceeded. Severe electrical disturbances can exceed the design specifications of the equipment. Electrical disturbances, glitches, affect the quality of electrical power. Common sources of these disturbances are:
Computer systems can be protected from the sources of many of these electrical disturbances by using:
Every precaution has been taken during power distribution system design to provide immunity to power outages of less than one cycle. However, testing cannot conclusively rule out loss of service. Therefore, adherence to the following guidelines provides the best possible performance of power distribution systems for server equipment:
This section describes wire selection and the types of raceways (electrical conduits) used in the distribution system. Wire size is dictated by circuit breaker sizing and local safety codes. Use copper conductors instead of aluminum, as aluminum’s coefficient of expansion differs significantly from that of other metals used in power hardware. Because of this difference, aluminum conductors can cause connector hardware to work loose, overheat, and fail. Raceways (electrical conduits) form part of the protective ground path for personnel and equipment. Raceways protect the wiring from accidental damage and also provide a heat sink for the wires. Any of the following types may be used:
All building feeders and branch circuitry should be in rigid metallic conduit with proper connectors (to provide ground continuity). Conduit that is exposed and subject to damage should be constructed of rigid galvanized steel. The IOX and Superdome or hp 9000 Superdome are safety grounded through the green (ground) wire in each AC power cord. In the IOX, this ground passes through the AC power cord entry into the XPC and connects internally to the XPC chassis. The XUC chassis and each ICE chassis are grounded through their respective DC power cords from the XPC. Additional safety grounding must be provided for networking equipment. Superdome servers require two methods of grounding:
The power distribution safety grounding system consists of connecting various points in the power distribution system to earth ground using green (green/yellow) wire ground conductors. Having these ground connections tied to metal chassis parts that may be touched protects computer room personnel against shock hazard from current leakage and fault conditions. Power distribution systems consist of several parts. Hewlett-Packard recommends that these parts be solidly interconnected to provide an equipotential ground to all points. The main electrical service entrance equipment should have an earth ground connection, as required by applicable codes. Connections such as a grounding rod, building steel, or a conductive type cold water service pipe provide an earth ground. To provide a continuous grounding system, all electrical conduits should be made of rigid metallic conduit that is securely connected together or bonded to panels and electrical boxes. Each power panel should be grounded to the electrical service entrance with green (green/yellow) wire ground conductors. The green (green/yellow) wire ground conductors should be sized per applicable codes (based on circuit over current device ratings).
Ground all computer equipment with the green (green/yellow) wire included in the branch circuitry. The green (green/yellow) wire ground conductors should be connected to the appropriate power panel and should be sized per applicable codes (based on circuit over current device ratings). Superdome was approved by regulatory agencies around the world, and therefore requires a ground/protective earth. there are no exclusions to this regulatory approval. High-frequency grounding between IOX and Superdome is provided by the cabinet-to-cabinet signal cabling. Whenever an IOX is connected to a Superdome cabinet, low-frequency grounding between these two cabinets is provided by a ground strap. This ground strap is shipped with each IOX. Refer to the I/O Expansion Cabinet Guide for more detail. The installation must provide a ground connection for the network equipment. This statement is translated into the following two languages as required:
If a raised floor system is used, install a complete signal reference grid (SRG) for maintaining equal potential over a broad range of frequencies. The grid should be connected to power source X0 and cabinet grounds as well as to other electrical service grounds. Flat braid offers superior frequency controls to round wire. Figure 5-1 “Raised Floor Metal Strip Ground System” illustrates a metallic strip grounding system.
HP recommends the following approaches:
Best Practices
HP recommendations concerning the proper grounding of a raised floor or signal reference grid are closely aligned with other agencies such as the NEC and IEEE. This section contains information about installation practices. Some common pitfalls are highlighted. Both power cable and data communications cable installations are discussed. Expansion and contraction rates vary among different metals. Therefore, the integrity of an electrical connection depends on the restraining force applied. Connections that are too tight compress or deform the hardware and causes it to weaken. This usually leads to high impedance causing circuit breakers to trip.
Wiring connections must be properly torqued. Many equipment manufacturers specify the proper connection torque values for their hardware. Ground connections must only be made on a conductive, nonpainted surface. Lockwashers must be used on all connections to prevent connection hardware from working loose. Power transformers and heavy foot traffic create high energy fields. Route data communications cables away from these areas. Use shielded data communications cables that meet approved industry standards to reduce the effects of external fields. Data cables that are run externally to a metal fire enclosure must have a minimum fire rating of VW-1 or VW-4 or better. The following environmental elements can affect a Superdome server installation:
The following guidelines are recommended when preparing a computer room for a Superdome server system:
Air conditioning equipment requirements and recommendations are described in the following sections. The cooling capacity of the installed air conditioning equipment for the computer room should be sufficient to offset the computer equipment dissipation loads, as well as any space envelope heat gain. This equipment should include:
Table 5-1 Controlled Computer Room Environment Specifications
Lighting and personnel must also be included. For example, a person dissipates about 450 BTUs per hour while performing a typical computer room task. At altitudes above 10,000 feet (3048 m), the lower air density reduces the cooling capability of air conditioning systems. If your facility is located above this altitude, the recommended temperature ranges may need to be modified. The following guidelines are recommended when designing an air conditioning system and selecting the necessary equipment:
The following three air conditioning system types are listed in order of preference:
A basic air distribution system includes supply air and return air. An air distribution system should be zoned to deliver an adequate amount of supply air to the cooling air intake vents of the computer system equipment cabinets. Supply air temperature should be maintained within the following parameters:
If a ceiling plenum return air system or a ducted ceiling return air system is used, the return air grille(s) in the ceiling should be located directly above the computer equipment cabinets. The following three types of air distribution system are listed in order of recommendation:
All air conditioning equipment, materials, and installation must comply with any applicable construction codes. Installation of the various components of the air conditioning system must also conform to the air conditioning equipment manufacturer’s recommendations. Figure 5-3 “Underfloor Air Distribution System” illustrates a typical computer room underfloor air distribution system (DRA). Figure 5-4 “Ceiling Plenum Air Distribution System” illustrates a typical computer room ceiling plenum air distribution system (CPRA). Figure 5-5 “Above Ceiling Ducted Air” illustrates a typical computer room above ceiling ducted air distribution system (DRA). Maintain proper humidity levels. High humidity causes galvanic actions to occur between some dissimilar metals. This eventually causes a high resistance between connections, leading to equipment failures. High humidity can also have an adverse affect on some magnetic tapes and paper media.
Low humidity levels are often the result of the facility heating system and occur during the cold season. Most heating systems cause air to have a low humidity level, unless the system has a built-in humidifier. Use separate computer room air conditioning duct work. If it is not separate from the rest of the building, it might be difficult to control cooling and air pressure levels. Duct work seals are important for maintaining a balanced air conditioning system and high static air pressure. Adequate cooling capacity means little if the direction and rate of air flow cannot be controlled because of poor duct sealing. Also, the ducts should not be exposed to warm air, or humidity levels may increase. Computer equipment can be adversely affected by dust and microscopic particles in the site environment. Specifically, disk drives, tape drives, and some other mechanical devices can have bearing failures resulting from airborne abrasive particles. Dust may also blanket electronic components like printed circuit boards causing premature failure due to excess heat and/or humidity build up on the boards. Other failures to power supplies and other electronic components can be caused by metallically conductive particles. These metallic particles are conductive and can short circuit electronic components. Use every effort to ensure that the environment is as dust and particulant free as possible. Smaller particles can pass though some filters and, over a period of time, possibly cause problems in mechanical parts. Small dust particles can be prevented from entering the computer room by maintaining its air conditioning system at a high static air pressure level. Other sources of dust, metallic, conductive, abrasive, and/or microscopic particles can be present. Some sources of these particulants are:
These pollutants are not always visible to the naked eye. A good check to determine their possible presence is to check the underside of the tiles. The tile should be shiny, galvanized, and free from rust. The computer room should be kept clean. The following guidelines are recommended:
Special precautions are necessary if the computer room is near a source of air pollution. Some air pollutants, especially hydrogen sulfide (H2S), are not only unpleasant but corrosive as well. Hydrogen sulfide damages wiring and delicate sound equipment. The use of activated charcoal filters reduces this form of air pollution. Metallic particulates can be especially harmful around electronic equipment. This type of contamination may enter the data center environment from a variety of sources, including but not limited to raised floor tiles, worn air conditioning parts, heating ducts, rotor brushes in vacuum cleaners or printer component wear. Because metallic particulates conduct electricity, they have an increased potential for creating short circuits in electronic equipment. This problem is exaggerated by the increasingly dense circuitry of electronic equipment. Over time, very fine whiskers of pure metal can form on electroplated zinc, cadmium, or tin surfaces. If these whiskers are disturbed, they may break off and become airborne, possibly causing failures or operational interruptions. For over 50 years, the electronics industry has been aware of the relatively rare but possible threat posed by metallic particulate contamination. During recent years, a growing concern has developed in computer rooms where these conductive contaminants are formed on the bottom of some raised floor tiles. Although this problem is relatively rare, it may be an issue within your computer room. Since metallic contamination can cause permanent or intermittent failures on your electronic equipment, Hewlett-Packard strongly recommends that your site be evaluated for metallic particulate contamination before installation of electronic equipment. Static charges (voltage levels) occur when objects are separated or rubbed together. The voltage level of a static charge is determined by the following factors:
Table 5-2 “Effect of Humidity on ESD Charge Levels” lists charge levels based on personnel activities and humidity levels. Table 5-2 Effect of Humidity on ESD Charge Levels
Follow these precautions to minimize possible ESD-induced failures in the computer room:
Computer equipment and air conditioning blowers cause computer rooms to be noisy. Ambient noise level in a computer room can be reduced as follows:
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|||||||||||||||