hp Integrity cx2600 Installation Guide: Regulatory Model Number: RSVLA-0303-DC > Chapter 5 Cable ConnectionsWire Selection and Terminal Lugs for Connection of DC Power |
|
A DC power terminal block is provided at the rear of each DC power supply. All four terminals (2+ and 2-) should be used. HP recommends a minimum #12 AWG or larger copper conductor be used for connecting DC power. The wire style and insulation type must be appropriately rated for the application. Aluminum conductors should be avoided. Aluminum has a coefficient of expansion that differs significantly from that of other metals commonly used in power hardware. Because of this difference, use of aluminum conductors can cause connector hardware to loosen, overheat, and fail. The terminal lugs used to connect DC power must be rated to handle the expected load of 15A/PSU. The width of the lug can be no larger than 0.3 inches (0.762 cm). |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|||||||||||||||