hp Carrier Grade Blade Server bh3710 Site Preparation Guide > Chapter 2 General System and Facility GuidelinesSystem Installation Guidelines |
|
This section contains information about installation practices. Some common pitfalls are highlighted. Both power cable and data communications cable installations are discussed.
Expansion and contraction rates vary among different metals. Therefore, the integrity of an electrical connection depends on the restraining force applied. Connections that are too tight compress or deform the hardware and cause it to weaken. This usually leads to high impedance preventing circuit breakers from tripping when needed or can contribute to a buildup of high frequency noise.
Wiring connections must be properly torqued. Many equipment manufacturers specify the proper connection torque values for their hardware. Ground connections must only be made on a conductive, nonpainted surface. When equipment vibration is present, lockwashers must be used on all connections to prevent connection hardware from working loose. Power transformers create high-energy fields in the form of electromagnetic interference (EMI). Heavy foot traffic can create electrostatic discharge (ESD) that can damage electronic components. Route data communications cables away from these areas. Use shielded data communications cables that meet approved industry standards to reduce the effects of external fields. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|||||||||||||||