This section provides electrical specifications for the hp
Integrity cx2600 Server.
Grounding |
 |
The site building shall provide a safety ground/protective
earth ground to all cabinets. A chassis ground point is provided
on the server rear panel. (See Figure 2-2 “Chassis Ground Lug”.)
Install a PE (protective earthing) conductor that is identical
in size, insulation material, and thickness to the branch-circuit
supply conductors. The PE conductor must be green with yellow stripes.
The earthing conductor is to be connected from the unit to the building
installation earth or, if supplied by a separately derived system,
at the supply transformer or motor-generator set grounding point.
System
Power Specifications |
 |
Table 2-3 “System Power Specifications” and Table 2-4 “System Power Requirements” list the power specifications for the
hp Integrity cx2600 Server. These tables provide information to
help determine the amount of power needed for your computer room.
Table 2-3 System Power Specifications
| Specification | Value |
|---|
| Nominal Input Voltage | -48VDC (-40 to -60
VDC) |
| Minimum Operating Voltage | -36 VDC |
| Maximum Operating Voltage | -72 VDC |
| Input Current | 12A DC typical (with VIN -48
VDC) |
| Input Power | 580W typical (@ 85% efficiency) |
| Maximum Inrush Current | 25 A |
| Maximum Output Current from each Power Supply | 49A DC for the 12V output3.5A DC for the V3.3sb
output |
| Efficiency | 82% (minimum) |
Table 2-4 System Power Requirements
| Power Required | Watts | Comments |
|---|
| Maximum configuration[1] | 650 | Maximum Theoretical |
| Typical configuration | 580 | |