This section provides the temperature/humidity requirements, noise emission, and air flow specifications for the HP Server.

Temperature and Humidity Specifications

Ambient intake air temperature is often different from ambient room temperature; you should measure the operating temperature and humidity directly in front of the cabinet cooling air intakes rather than just checking ambient room conditions.

Table 8-6 Computer Environment

ParameterOperating RangeRecommended Operating RangeMaximum Rate of ChangeNon-Operating Range
Temperature5oC to 35oC (up to 5,000 feet)20oC to 25oC (up to 5,000 feet)10oC/hr with tape 20oC/hr without tape-40oC to +70oC
Relative humidity15% to 80% at 35oC noncondensing40% to 60% at 35oC noncondensing30% per hour noncondensing 

 

NOTE: Operating ranges refer to the ambient air temperature and humidity measured at the cabinet cooling air intake vents.

Acoustic Noise Specification

The acoustic noise specification for the hp Integrity rx5670 is as follows:

  • < 60 db LpA (sound pressure level at bystander position)

The above level is appropriate for dedicated computer room environments, not office environments.

Care should be taken to understand the acoustic noise specifications relative to operator positions within the computer room or when adding hp Integrity rx5670 to computer rooms with existing noise sources.

Air Flow

The recommended cabinet air intake temperature is between 68oF and 77oF (20oC and 25oC) at 960 CFM.